Instructions for Use, Installation and Servicing ecoMAX pro 29
16 Combustion analysis 17 Fault finding
Again in screen ‘8’, Set the appliance fan speed/burner to
minimum by pressing the ‘-‘ key until ‘1’ (burner to Pmin)
is shown on the right hand side of the screen. Press the
‘mode’ button again.
* ecoMAX pro 28E only - for LPG see page 23
Fig 14.5
12706
Check the CO
2
value, which should be 8.8 % ± 0.2 %. If
adjustment proves necessary then proceed as follows.
Adjustment of the CO
2
at minimum rate is very
coarse, so carefully adjust the CO
2
with the (‘B’) offset
adjustment using a 2mm allen key to 8.8 %, (rotate
clockwise to increase).
After checking the combustion, press and hold the ‘mode’
button for 10 seconds to return to the normal mode,
showing the current flow temperature. Replace the cap
on the sampling point and refit the outer front case.
NOTE:
Depending on the time to take the readings, the
display may default back to the normal mode, it
may be necessary to repeat steps 3,4 and 5 to
adjust the appliance fan speed/burner.
18E 28E *
Output Min Max Min Max
Burner % CO
2
Case on (± 0.2) 9.0 9.0 9.0 9.0
Case off (± 0.2) 8.8 8.8 8.8 8.8
Approx. gas rate
(after 10 mins 0.53 2.00 0.56 3.02
from cold) m
3
/h
Fault Finding
Logical fault finding procedure
These checks must be carried out before attempting to
use the fault finding guide.
1. Carry out electrical safety checks (see section
‘preliminary electrical checks’ 13.1).
2. Check that the external electricity supply to the boiler is
on, and a supply of 230V is present at the boiler
terminal strip.
3. Check that the gas supply to the boiler is on, that it
has been correctly purged and that an inlet pressure of
20mbar is available at the gas valve (see section ‘gas
supply’ 13.3).
4. Check that the main on/off control is set to the ‘on’
position.
5. Set the central heating temperature to maximum.
6. Check that all external controls are on and calling for
heat.
7. Check that all manual circuit controls ie. bypass,
radiator valves are correctly adjusted.
17.1 Status Mode
A series of status mode screens are available for current
boiler operating information.
To display the status mode, proceed as follows:
With the interface in ‘normal’ mode, press and hold the
‘mode’ button (
) for 10 seconds until a flashing ‘0’
appears (fig. 17.1).
Press the ‘-‘ key and scroll through until ‘96’ (installer
mode) is shown on the screen, then press the ‘mode’
button again.
A series of screens are then available for service
functions. An example is shown in fig. 17.2 (screen 23
‘product code’ for the ecoMAX pro 18E).
Fig 17.1
12713
Fig 17.1
12714